Fire Alarm System 13 :

Zoning: An important consideration when designing fire alarms is that of individual zones. Specifically: A single zone should not exceed 2,000m² in floor space. Where addressable systems are in place, two faults should not remove protection from an area greater than 10,000m². A building may be viewed as a single zone if the floor space is less than 300m². Where the floor space exceeds 300m² then all zones should be restricted to a single floor level. Stairwells, lift shafts or other vertical shafts (non stop risers) within a single fire compartment should be considered as one or more separate zones. The maximum distance traveled within a zone to locate the fire should not exceed 60m